DuraVent

MODEL BV

Type B Gas Vent Systems

Our non-positional lock system on the DuraVent® BV Gas Vent is the best lock system on the market today. The incorporation of the DuraTab® feature simply improves our lock system by adding flexibility and meeting market needs.

The BV line of DuraVent round vent pipe and fittings is designed for use on approved gas appliances in residential and light commercial and industrial applications.

DuraLock® Locking System

GroupImage_BV
ItemClearance - See Note 1Max HeightOuter Tube ØMaterialsLocking DeviceUL Listing
Type B Vent Round 3″-8″ (USA)1 inch100 feet1/2″ larger than IDInner – .012″ Aluminum Outer – .018″ GalvanizedDuraLock & DuraTabMH2848
Type B Vent Round 3″-8″ (CAN)1 inch100 feet1/2″ larger than IDInner – .012″ Aluminum Outer – .018″ Galvalume*DuraLock & DuraTabMH2848
Round 10" to 18" - See note 21 inch100 feet1″ larger than IDInner – .014″ Aluminum Outer – .018″ GalvanizedDuraLockMH2848
Round 20″ to 30″ (USA) See note 21 inch100 feet1″ larger than IDInner – .023″ Aluminum Outer – .018″ GalvanizedDuraLockMH2848
Round 20″ to 24″ (CAN) See note 21 inch100 feet1″ larger than IDInner – .023″ Aluminum Outer – .018″ GalvanizedDuraLockMH2848
Round 26″ to 30″ (CAN) See note 22 inch100 feet1″ larger than IDInner – .023″ Aluminum Outer – .018″ GalvanizedDuraLockMH2848
Oval Type B Gas Vent 4″ and 5″1 inch - See Note 5See Note 34": 2 1/2″ x 7 1/4″ or 5": 3 1/8″ x 10 7/8″Inner – .012″ Aluminum Outer – .018″ GalvanizedDuraLockMH2848
Oval Type B Vent 6″1 inch - See Note 5See Note 33 1/4″ x 12″Inner – .012″ Aluminum Outer – .018″ GalvanizedDuraLockMH2848
DuraConnect I Flex 3″ and 4″1 inchSee Note 4NA.012″ Aluminum Flexible .018″ Galvalume FittingsDuraLock & DuraTabMH17667
DuraConnect II Flex 3″ to 5″1 inchSee Note 41/4″ larger than ID.006″ 2 Ply Aluminum Flex .018″ Galvalume FittingsDuraLock & DuraTabMH17667

*In Canada, the outer tube material is galvalume for 3″ to 8″ pipe length. All other 3″ to 8″ fittings have a galvanized outer tube.

Notes: Gas Vent Specification Chart

  1. Clearance to combustibles is the air space between vent and combustibles.
  2. For maximum height refer to the appliance manufacturer installation instructions and the National Fuel Gas Code NFPA 54 or the Canadian Fuel Gas Installation Code CSA-149.1-00. For taller applications refer to DuraVent Sizing Handbook.
  3. When oval is used on wall furnaces, minimum height required from bottom of furnace to cap is 12′, minimum 16″ stud space.
  4. Limited by sizing tables.
  5. BVO 4″ & 5″ oval can be installed in a 2″ x 4″or a 2″ x 6″ stud wall. BVO 6″ oval can be installed in a 2″ x 6″ stud wall.